GENERAL INFORMATION | AHSC-1000 |
Primary Power | PoE 802.3at / 9 - 24 VDC ± 20%, 550 mA maximum (reader current not included) |
Primary Host Communication |
Ethernet: 100Base-TX 256bit AES* symmetric encryption for Controller to Server and Inter-Controller communications |
Secondary Host Communication | Secondary Host Communication |
Third Host Communication |
Wi-Fi IEEE 802.11ac 5GHz, or 2.4GHz/5GHz IEEE 802.11n 256bit AES* symmetric encryption for Controller to Server and Inter-Controller communications |
Ethernet network connection |
Port 1: Ethernet: 100Base-TX Port 2: Ethernet: 100Base-TX (Configurable for Port Failover) |
RS-485 connection |
Port 1: Armatura RS-485 / OSDP V2.2 Port 2: Armatura RS-485 / OSDP V2.2 Port 3: Armatura RS-485 / OSDP V2.2 (Configurable for Port Redundancy dedicated on port 2 & 3) |
Number of Ports |
2*TCP/IP (IPv4 & IPv6) 3*RS-485 2*Wiegand 1*RS-232 |
Inputs |
4 states supervision, resistor values (5% tolerance), Normally open contact: use 1.2k, 2.2k. 4.7k or 10k Normally closed contact: use 1.2k, 2.2k. 4.7k or 10k Dedicated Panel Tamper IO Input* Dedicated Microchip Control Fire Alarm IO Input & REX Input for catastrophic situation |
Outputs |
1 relay, 1* Form-C with dry contacts |
Normally Open Contact Rating | 5A @ 30Vdc resistive |
Normally Closed Contact Rating | 5A @ 30Vdc resistive |
On-Board Monitor |
Size: 2.4", Resolution: 320*240, TFT Monitor Quickly view status of board, connected doors and for configuration information display |
On-Board Webserver |
Webserver for System Configuration and Management Dashboard for Controller Status Monitoring, Device Connection Status Monitoring & Configuration, Performance Status, Server Primary Controller Setting, Network Status Monitoring & Setting, IP Access Filter, SSL / TLS Certificates Setting, Access Log Export, Controller Reset, Debug Status Monitoring, Operation Log Monitoring, User Management, Date & Time Setting, Daylight Saving Time Setting, NTP Server Setting, General Status, Controller Information |
RFID Card Capacity |
As a Main-Controller: 800,000 (Storage) As a Door Unit: 400,000 (1:N) / 800,000 (1:1) |
Maximum RFID Card Number Length | Maximum RFID Card Number Length |
Mobile Credential Capacity |
400,000 (1:N) (Bluetooth) 400,000 (1:N) (NFC) 400,000 (1:N) (Dynamic QR Code) |
Fingerprint Capacity |
As a Primary Controller: 100,000 (Storage) As a Door Unit: 50,000 (1:N) / 100,000 (1:1) |
Face Capacity |
As a Primary Controller: 100,000 (Storage) As a Door Unit: 5,000 (1:N) / 100,000 (1:1) |
Palm Capacity |
As a Primary Controller: 5,000 (Storage) As a Door Unit: 3,000 (1:N) / 5,000 (1:1) |
Transaction Buffer |
5,000,000 Events |
Access Level |
100,000 Levels |
On-Board Access Point Control |
1 access point on board |
On-Board Reader Support | 2 (OSDP over RS-485) or 2 (Wiegand) with on-board IO |
Maximum Access Point |
129 (with 32pcs AHDU-1460 modules through TCP/IP connection) 97 (with 24pcs AHDU-1460 modules through Armatura RS-485 over RS-485 connection) |
Maximum Readers |
258 (with 32pcs AHDU-1460 modules through TCP/IP connection) 194 (with 24pcs AHDU-1460 modules through Armatura RS-485 over RS-485 connection) |
Maximum Inputs |
12,801 (with 33pcs AHDU-1460 modules through TCP/IP connection + 792pcs AHEB-1602 IO Expansion Board through OSDP over RS-485 connection) |
Maximum Outputs |
12,801 (with 33pcs AHDU-1460 modules through TCP/IP connection + 792pcs AHHEB-0216 IO Expansion Board through OSDP over RS-485 connection) |
Maximum IO Board |
24pcs (2*High Speed RS-485 communication) |
Maximum DU Modules |
32pcs (1*TCP/IP communication with AES-256 & TLS1.2 end to end secure channel) 24pcs (OSDP over RS-485 communication with AES-128 end to end secure channel) |
DOOR UNIT CONTROLLER INTERFACE | |
Input Voltage | 12 -24 Vdc +/- 10% regulated, 500 mA maximum each reader |
Maximum Input Current | 12 -24 Vdc +/- 10% regulated, 500 mA maximum each reader |
TCP/IP Mode |
Ethernet: 100Base-TX |
TCP/IP Protocol | 802.1X, VLAN, SSH, IPv4, IPv6, WebSocket |
TCP/IP Encryption | Complied up to TLS1.2, AES-256 end to end secured communication channel |
TCP/IP Communication | Spada Protocol over WebSocket |
RS-485 Protocol | AES-256, Armatura RS-485 Secure Channel |
Armatura RS-485 Mode |
9600-115200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit. |
Data Inputs |
TCP/IP standard supported. Maximum TCP/IP cable length: 330ft. (100m) RS-485 standard supported. Maximum RS-485 cable length: 3937ft. (1200m) |
RFID / BIOMETRICS READER INTERFACE | |
Input Voltage | 12 -24 Vdc +/- 10% regulated, 500 mA maximum each reader |
Maximum Input Current | 12 -24 Vdc +/- 10% regulated, 500 mA maximum each reader |
RS-485 Protocol | AES-128, OSDP Secure Channel |
OSDP Mode |
9600-115200 bps, OSDP V2.2, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit. 3rd Party reader: support OSDP V2.2 or above |
Wiegand | Read: support up to 128 bits / Write: Support 26 / 34 / 37 bit, and other customised card formats |
Tamper Input (Wiegand) | TTL levels, high > 3 V, low < 0.5 V, 5 mA source/sink maximum |
Buzzer Output (Wiegand) | TTL levels, high > 3 V, low < 0.5 V, 5 mA source/sink maximum |
LED Output (Wiegand) |
TTL levels, high > 3 V, low < 0.5 V, 5 mA source/sink maximum |
Data Inputs |
RS-485, OSDP and Wiegand standards supported. Maximum RS-485 /OSDP cable length: 3937ft. (1200m) Maximum Wiegand cable length: 328ft (100m) |
IO EXPANSION BOARD INTERFACE | |
RS-485 Protocol | TLS 1.2, AES-128, OSDP V2.2 Secure Channel |
OSDP Mode |
9600-115200 bps, OSDP V2.2, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit. Maximum cable length: 2,000 ft. (609.6m) |
Data Inputs | OSDP and Wiegand standards supported. Maximum cable length: 500 ft. (152m) |
SOFTWARE INTERFACE | |
TCP/IP Mode | Ethernet: 100Base-TX |
TCP/IP Protocol | NTP, SNMP V2 /V3, 802.1X, vLan, SSH, MQTT, IPv4, IPv6, DNS, DDNS |
TCP/IP Encryption |
Complied up to TLS1.2, AES-256 end to end secured communication channel |
TCP/IP Communication | Spada Protocol over MQTT |
CABLE REQUIREMENT | |
Power & Relays | One twisted pair, 18-16 AWG |
Ethernet |
CAT-5, minimum 330 ft. (100m) |
Ethernet Failover Port | CAT-5, minimum 330 ft. (100m) |
RS-485 Reader Port |
9600-115200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit. One twisted pair with drain wire and shield, 120 ohm resistance, 22-18 AWG, Maximum cable length: 3937ft (1200m) |
RS-485 I/O Device Port |
9600-115200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit. One twisted pair with drain wire and shield, 120 ohm resistance, 22-18 AWG, Maximum cable length: 3937ft (1200m) |
RS-485 Failover Port |
9600-115200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit. One twisted pair with drain wire and shield, 120 ohm resistance, 22-18 AWG, Maximum cable length: 3937ft (1200m) |
Wiegand Port | 20 AWG shielded Wiegand wire ,328ft. (100m) |
MECHANICAL | |
Dimensions | 4.8” W x 10.2” L x 2.5” H in. (122 x 260 x 62.5mm) |
Weight | approx. 30oz (830g) |
Mounting |
Supported DIN35 Rail Compatible with UTA89 Din Rail Adapter for screwing on switchgear (Sold Separately) Wall mount |
Housing Material | ABS-PC UL-94 V2 |
ENVIRONMENTAL | |
Temperature | 22°F ~ 158°F (-30°C~70°C), Operating & Storage |
Humidity |
0-95%RHNC |
Certification(s)* |
CE, FCC, RoHS, UL294 |
Security Rating |
Secure Data Storage in EAL 6+ Certified Crypto Chip |
SOFTWARE | |
Supported Software |
Armatura-One Security System |